Product Details:
Payment & Shipping Terms:
|
Material: | Copper | Core: | Single |
---|---|---|---|
Sheath: | Copper | Application: | Industrial |
Field: | Civil | Certificate: | ISO9001-2015 |
High Light: | mineral insulated wire,mineral insulated heating cable |
600 Volt Rated Voltage Copper Sheathed Mineral Insulated Heating Cable is a 600 volt rated voltage with a copper sheathed mineral insulated heating cable. Copper sheathed series mineral insulated heating cables can meet the needs of high temperature conditions and heat tracing along long-distance pipelines. Copper sheathed heating cable (MICU) manufactured by Pasia can sustain the highest temperature up to 250 ℃. Conductor resistance value ranges from 480 Ω Ω/km to 0.5 / km. For application occasions like in corrosion or buried, Copper Sheathed Mineral Insulated Heating cable covered with High Density Polyethylene (HDPE) outer sheath (MIHC) can sustain the highest temperature up to 90 ℃. Mineral insulated cable possesses excellent mechanical strength. Various powder requirement can be realized based on Pasia’s series resistance heating cable.
Application:
Copper Sheathed Mineral Insulated Heating Cable | Maximum Output Power(W/m) |
Freezing Proof on Metal Gutters and Downspouts | 49 |
Freezing Proof on Non-metal Gutters and Downspouts | 16 |
Process Temperatures Maintenance for Vessel and Piping | 59 |
Freezing Prevention on Metal Containers and Pipes | 59 |
Snow Melting on Metal Roof | 49 |
Heating Cable of High-Density Polyethylene Jacket Copper Sheathed (MIHC) | |
Freezing Prevention on Metal Containers and Pipes | 26 |
Freezing Prevention on Non-metallic Containers and Pipes | 13 |
Snow Melting of Asphalt Slope | 82 |
Snow Melting of Non-metal Roof | 26 |
Freezing Proof on Metal Gutters and Downspouts | 26 |
Freezing Proof on Non-metal Gutters and Downspouts | 16 |
Heating of Concrete Floor | 33 |
Defrosting for Ground Uplift Prevent of Cold Storage | 23 |
Snow Melting for Concrete and Asphalt Pavement | 99 |
Note: when the heating cable is used for vessel and pipe heat tracing, the maximum output power must be controlled to ensure that the sheath temperature does not exceed its maximum withstand temperature or the spontaneous combustion temperature of that section (for dangerous areas).
Heating Element Structure
Heating Cable Specification(600V Single Core)
Cable Code | Diameter | +20℃ Standard Resistance | Maximum Manufacturing Length | Unit Weight |
mm | Ω/m | m | kg/km | |
16C5 | 11.9 | 0.0005 | 190 | 787.1 |
16C6 | 11.4 | 0.0006 | 200 | 718.9 |
16C7 | 10.8 | 0.0007 | 210 | 648.7 |
16C9 | 10.3 | 0.0009 | 250 | 575.8 |
16C11 | 9.5 | 0.0011 | 300 | 487.8 |
16C13 | 9.1 | 0.0013 | 315 | 441.1 |
16C17 | 8.6 | 0.0017 | 350 | 391.9 |
16C22 | 8.2 | 0.0022 | 380 | 357.1 |
16C29 | 7.8 | 0.0029 | 400 | 320.1 |
16C43 | 6.9 | 0.0043 | 430 | 240 |
16C57 | 6.6 | 0.0057 | 450 | 219.2 |
16C69 | 6.4 | 0.0069 | 460 | 208.1 |
16C86 | 6.2 | 0.0086 | 480 | 196.2 |
16C115 | 6.0 | 0.0115 | 500 | 183.3 |
16C172 | 5.7 | 0.0172 | 500 | 168.9 |
16C246 | 5.5 | 0.0246 | 500 | 158.9 |
16K369 | 9.1 | 0.0369 | 170 | 441.1 |
16K480 | 8.2 | 0.0480 | 220 | 345.1 |
16K600 | 7.8 | 0.0600 | 280 | 312.5 |
16K800 | 7.4 | 0.0800 | 370 | 277.8 |
16K1200 | 6.9 | 0.1200 | 560 | 240 |
16K1600 | 6.6 | 0.1600 | 750 | 219.2 |
16K1920 | 6.4 | 0.1920 | 900 | 208.1 |
16K2400 | 6.2 | 0.2400 | 1000 | 196.2 |
16K3200 | 6.0 | 0.3200 | 1100 | 183.3 |
16K4800 | 5.7 | 0.4800 | 1200 | 168.9 |